Technical FAQs

Ask a Question

What are the Twido Compact power supply specifications?

The following table provides power supply information for the Compact controller.

ITEM
SPECIFICATIONS
Power supply voltage Rated power voltage; 100 to 240 vac.
Allowable range; 85 to 264 vac.
Failure - depends on quantity of used inputs and output points. Generally, failure is detected when voltage drops below 85 vac, stopping operation to prevent malfunction.
NOTE: Momentary power interruption for 20 ms or less at 100 to 240 vac is not recognized as a failure.
Inrush current flow at power-up TWDLCAA10DRF and TWDLCAA16DRF 35 Amp maximum
TWDLCAA24DRF 40 Amps maximum
Power supply wiring UL1015 AWG22 (0.64 mm) or UL1007 AWG18 (1.02mm) Make the power supply wiring as short as possible.
Ground wiring UL1007 AWG16 (1.30 mm) Do not connect ground wire in common with ground wore of motor EQUIPMENT.

Legacy KB System (APS) Data: RESL2138 V1.0, Originally authored by on , Last Edited by on
Related ranges: Twido
Was this helpful?
What can we do to improve the information ?