Does the BMXAMI0800 or BMXAMI0810 required an external loop power supply or does the module provide it for the 4-20mA current loops ?

Yes, both the BMXAMI0800 and the BMXAMI0810 require an external loop power supply for their 4-20mA current loops. The module does not provide it.


Legacy KB System (APS) Data: RESL212038 V1.0, Originally authored by DaSo on 07/12/2013, Last Edited by DaSo on 07/12/2013
Related ranges: Modicon M340