What is the maximum bus length for the Quantum 140EIA92100 AS-i module?


        • Max length of the bus": 100m.
          Possibility to extend the bus through repeaters (+supplies): 2 repeaters max between the master and a slave (300m).
          Scan Time: 5ms with 31 stations / 10ms with 62 stations with extended profile.

Legacy KB System (APS) Data: RESL211305 V1.0, Originally authored by DiSa on 05/02/2013, Last Edited by DiSa on 05/02/2013
Related ranges: Modicon Quantum