What causes Unity Pro error "ObjectStore internal error. VirtualAlloc failed to allocate any address - Not enough storage is available to process this command (8)"?

Use the Registry editor browser (Regedit) to access to the following parameter:
HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\COMMON\ObjectStoreParam

Double click on AddressingSpaceSize
The default value is 0x28000000.
Modify this value to 0x18000000.


Legacy KB System (APS) Data: RESL210923 V1.0, Originally authored by DaSo on 03/09/2013, Last Edited by DaSo on 03/09/2013