Web Designer project cannot be transferred from the module.

Goals and Symptoms

Web Designer project cannot be transferred from the module.

Facts and Changes

All Factorycast, Factorycast HMI and Factorycast Gateway mdoules

Causes and Fixes

If the user is unable to transfer the application from the module because the exec fimrware version in the module is newer than the one in the Web Desinger project, they can perform a target upgrade (click on 'Target\Upgrade Target Version'). During a target update, the software scans the hardware for differencesand modifies the respective exec fimware files in the project to match what is in the module. If the newer exec firmware files are not installed in Web Designer, the 'Target\Upgrade Target Version' selection will only upgrade to the latest version that is installed in Web Designer (The 'Transfer' button will still be greyed out). To resolve this issue, the updated Web Designer software must be installed.