Technical FAQs

Ask a Question

NOE311 does not work with the 'MBP_MSTR'

Goals and Symptoms

'140NOE311' module does not work with the 'MBP_MSTR' function block

Facts and Changes

140NOE31100

Causes and Fixes

If you try to use the 'Read CTE' option for the 'MBP_MSTR' block to read the information from a 'Symax' drop using an
'140NOE31100', the error 7001Hex will get returned.

The reason that the error gets returned is because the '140NOE31100' is not supported on the MBP_MSTR block for
Unity.

The '140NOE31100' will only work with the MSTR function block for the 984 ladder logic in either Modsoft, Concept,
'ProWORX Nxt' or 'ProWORX 32'. It will not work in Unity.

Was this helpful?
What can we do to improve the information ?