How to configure the STBEHC3020 for event counting

Goals and Symptoms

How to configure the EHC3020 for event counting.

Facts and Changes

All versions of the Advantys Configuration Software.

Causes and Fixes

Wire the 'EHC3020' to the incremental encoder.


  • Double click on the 'EHC3020' module to open the properties window for the module.
  • Configure the parameters as shown.
· Download the application to the island.

 
  • Start the PLC.
· Place the PLC into test mode.
  • Set the Input Validation bits to Off.
  • Set the Counter Enable to On.

Legacy KB System (APS) Data: RESL200117 V1.0, Originally authored by AlCh on 09/28/2009, Last Edited by AlCh on 09/28/2009