Technical FAQs

Ask a Question

How to configure the STBEHC3020 for modulo mode

Goals and Symptoms

How to configure the STBEHC3020 for modulo mode.

Facts and Changes

All versions of the Advantys Configuration Software.

Causes and Fixes

 

  • Wire the 'STBEHC3020' to the incremental encoder.



  • Double click on the 'STBEHC3020' module to open the properties window for the module.


· Configure the parameters as shown.
· Download the application to the island.


· Start the PLC.
· Place the PLC into test mode.


Set the Input Validation bits to Off.


Set the Counter Enable to On.


Set the Counter Sync bit to On.


To reset the counter, toggle the counter sync bit from 0 to 1.

Legacy KB System (APS) Data: RESL199710 V1.0, Originally authored by AlCh on 08/26/2009, Last Edited by AlCh on 08/26/2009
Related ranges: Advantys STB
Was this helpful?
What can we do to improve the information ?