TCSESM ConneXium Switches and FW version 4.1

Goals and Symptoms

Users of ConneXium TCSESM switches may experience a failure of the Web pages to function properly.

Facts and Changes

Issue was identified and will be addressed in future versions.

Causes and Fixes

On your PC select Start->Settings->Control Panel->Java. This will open the Java Control Panel. Select the Advanced tab. Expand the Java Plug-in Branch and de-select the box (Enable the next-generation Java Plug-in). Click the OK button.


Legacy KB System (APS) Data: RESL199674 V1.0, Originally authored by PeZa on 08/21/2009, Last Edited by PeZa on 08/21/2009
Related ranges: ConneXium - Ethernet