Technical FAQs

Ask a Question

Maximum Number of I/O Modules in an STBNIP2212 Island Segment

Goals and Symptoms

The purpose of this Resolution is to inform users of Advantys STBNIP2212 Ethernet NIMs that the specification for "addressable modules supported" per segment is incorrect.

Causes and Fixes

The STBNIP2212 Applications Guide, part number 31003688, states the 'addressable modules supported' per segment is 16. This number is incorrect.

Although up to 6 segments can configured in an island, there is no limitation to the number of I/O modules in a segment. The only limitation is the maximum number of I/O modules in an island is 32.


Legacy KB System (APS) Data: RESL198292 V1.0, Originally authored by DaDz on 04/16/2009, Last Edited by DaDz on 04/16/2009
Related ranges: Advantys STB
Was this helpful?
What can we do to improve the information ?