Importing a Modsoft program returns 'Convert' error

Goals and Symptoms

Importing a Modsoft program returns 'Convert' error.

Facts and Changes

ProWORX 32 version 2.1

Causes and Fixes


Importing a Modsoft program returns 'Convert' error:


which is followed by:


The error will get returned if the Modsoft program contains a custom loadable. To resolve the
problem,

  • Delete the custom loadable from the program using Modsoft
  • Save the changes.
  • Import it the Modsoft program using ProWORX 32'.

During the import, you may get the following warning message because the converter does not
recognize the custom loadable block that is in the logic. You should compare the logic from the
Modsoft program against the 'ProWORX 32' project to ensure that everything is fine with the
exception of the deleted custom loadable nodes or blocks.

Legacy KB System (APS) Data: RESL191758 V1.0, Originally authored by AlCh on 04/23/2008, Last Edited by AlCh on 04/23/2008