BootP doesn't not work after updating to Exec Firmware version 4.1

Goals and Symptoms

BootP doesn not work after updating to Exec Firmware version 4.1

Facts and Changes

140NOE77101 version 4.1 and greater.

Causes and Fixes

The reason why this happens is because a verification step was added in 'Exec Frimware version 4.1'
This step caused the 140NOE77101 to perform a check for the subnet mask other than 000.000.000.000.
To resolve the problem, specify a subnet mask in the bootp configuration.


Legacy KB System (APS) Data: RESL191455 V1.0, Originally authored by AlCh on 03/26/2008, Last Edited by AlCh on 03/26/2008