No selection for STB is found after starting the Advantys Configuration Software.

Goals and Symptoms

The 'STB' bttuon cannot be found after starting the 'Advantys Configuration Software' even though the
'STB' option was selected during the install process.

Facts and Changes

All versions of the 'Advantys Configuration Software'.

Causes and Fixes

The 'STB' bttuon cannot be found after starting the 'Advantys Configuration Software' even though the
'STB' option was selected during the install process.



This problem will happen if the registry settings did not get properly written during the installation process
as a result of a corrupted registry or the user not having full administrative rights to the PC.

To resolve the problem:

  • Click on 'Start\Run'
  • Type in 'regedt32' to open the Windows registy.

WARNING: BE VERY CAREFUL WHEN USING THE REGUSTRY EDITOR IF THESE STEPS ARE NOT FOLLOWED EXACTLY,
YOU MAY INADVERTENTLY DELETE SOMETHING ELSE WHICH CAN CORRUPT YOUR WINDOWS OPERATING
SYSTEM.

  • Check the 'HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\Advantys\Settings' Windows
registry key to see if the settings are similiar to what is shown as below.


If the settings are not correct:
  • Uninstall the Advantys Configuration Software.
  • Reboot the PC
  • Clean the registry.
  • Reboot the PC.
  • Log in as an administrator.
  • Re-install the software.

Legacy KB System (APS) Data: RESL190573 V1.0, Originally authored by AlCh on 01/09/2008, Last Edited by AlCh on 01/09/2008
Related ranges: Advantys STB