Error "proworxaddrused.frm" when trying to open a Project after installing 'Proworx 32'

Goals and Symptoms

The error "proworxaddrused.frm" gets returned when trying to open a project

Facts and Changes

All versions of Proworx 32

Causes and Fixes

This error will get returned if you updated to a patch immediately after installing 'ProWORX 32' without
rebooting the PC.

To resolve the problem,

  • Insert the installation CD and start the install process.
  • Select the repair option to perform a repair.
  • Reboot the PC.
  • Apply the patch update.

Legacy KB System (APS) Data: RESL190343 V1.0, Originally authored by AlCh on 12/12/2007, Last Edited by AlCh on 12/12/2007