TwidoPort 499TWD01100 Exec Upgrade to v.3.02

Release Notice

The purpose of this resolution is to inform TwidoPort 499TWD01100 product users that the Exec has been upgraded to version 3.02.

Goals and Symptoms

Twidoport modules would randomly lose their IP address or go into Kernel mode and require user intervention to become operational again. A lost IP address could be recovered by power cycling the module. To recover from a Kernel Mode failure, a Telnet login would be required to put the module into Run.

Causes and Fixes

Version 3.02 is more tolerant of Broadcast traffic (ARP, NetBIOS, IPX/SPX, NetBEUI) than previous Exec versions. If the tolerance levels are reached within the module. the unit will reboot without user intervention.

Also reference DMDI 1688E.


Legacy KB System (APS) Data: RESL187543 V1.0, Originally authored by DaDz on 08/14/2007, Last Edited by DaDz on 08/14/2007