Technical FAQs

Ask a Question

Bad number of segments gets returned after changing the configuration

Goals and Symptoms

Bad number of segments gets returned after changing the PLC configuration

Facts and Changes

ProWORX 32 version 2.0C

Causes and Fixes

If you make a change to the PLC Configuration in the Offline mode and try to start the PLC
after downloading it, the error 'Bad number of segments' could get returned. This could happen
when the defined number of segments is smaller than 32 and the PLC type is changed or a change
is made in the 'Loadables' for the project. The segments may also appear to be out of order
when they are veiwed from the network navigation window after downloading the project.

To resolve the problem, switch to the 'Offline' mode, change the number of segments in the
Configuration window to the maximum number of 32, save the changes and download the project
to the PLC..


Legacy KB System (APS) Data: RESL184083 V1.0, Originally authored by AlCh on 05/18/2007, Last Edited by AlCh on 05/18/2007
Related ranges: ProWORX
Was this helpful?
What can we do to improve the information ?