Technical FAQs

Ask a Question

STBACO1210 Loop Current Maximum Load Impedance

Goals and Symptoms

The purpose of this resolution is to inform users of STBACO1210 analog output modules of the Maximum Load Impedance specification.

Facts and Changes

The Maximum Load Impedance value defines the maximum impedance allowed in the current loop so currents of 20ma can be provided by the module.

Causes and Fixes

The Maximum Load Impedance specification for the STBACO1210 analog output module is less than or equal to 500 ohms resistive. Load impedance values greater than 500 ohms can prevent the module from producing currents up to 20ma.


Legacy KB System (APS) Data: RESL183484 V1.0, Originally authored by DaDz on 04/12/2007, Last Edited by DaDz on 04/12/2007
Related ranges: Advantys STB
Was this helpful?
What can we do to improve the information ?