What does error 151 generated by the Xxmit block mean?


Error 151 indicates the variables associated with MsgOut / MsgIn parameters are not long enough. When the Xxmit block is being used as a Modbus messaging function the MsgIn and MsgOut parameters must be configured as located variable of type Word Array 9.