Technical FAQs

Ask a Question

Why is the ERR LED on my TSX07 Nano PLC flashing?

The ERR LED on the TSX07 Nano PLC will flash if the program application is either absent or is not executable. To recover from this, log in with PL7-07 and reload the application. If the problem persists check PL7-07 for any error messages.


Legacy KB System (APS) Data: RESL170774 V1.0, Originally authored by on , Last Edited by on
Related ranges: TSX07
Was this helpful?
What can we do to improve the information ?