Does Unity Pro provide system bits to monitor the batteries in the high end Quantum PLCs?

%s67 described as PCMCIABAT0 in Unity Pro monitors the state of the PCMCIA card A application memory battery card. (TSX BATM01).
%s75 described as PCMCIABAT0 in Unity Pro monitors the data storage memory PCMCIA card B battery card. (TSX BATM01).
%s68 described as PLCBAT in Unity Pro monitors the CPU battery in the back of the front panel of the CPU.
If this system bits are set to 0, the battery is present and operational.
The small battery of the PCMCIA card (TSX BAT M03) has no diagnostic available.