What are the minimum and maximum cable specifications for Remote I/O ( RIO )?

Maximum drop length is 164 feet.
Minimum drop length is 8.5 feet.
Maximum trunk length is 8400 feet using RG11 and 4600 feet using RG6.
Maximum overall attenuation for the network is 35 db.
Minimum distance between taps is 8.5 feet.
Minimum distance between the RIO head and the self terminating "F" adapter is 18 inches.
Minimum distance between the self terminating "F" adapter and splitter 8.5 feet.


Legacy KB System (APS) Data: RESL167487 V2.0, Originally authored by GeMc on 08/24/2013, Last Edited by DiSa on 08/24/2013
Related ranges: Modicon 1/2/3/4/5/8/984s