Technical FAQs

Ask a Question

How do I Configure the Slot ID in a Quantum 140-CPU-6xx-xx Ethernet configuration?

The high byte of fifth configuration register for the MBP_MSTR block is used to define which backplane slot position the Ethernet module resides in.
The older Quantum controllers had a single slot Ethernet head module so the high byte of that register would be set to the slot number in which the NOE resides.

The new Quantum 140-CPU-6xx-xx controllers have a built in Ethernet port and the controller itself is two slots wide.

The high byte is not set to neither to slot three or slot four; rather a code of FE Hex is used to indicate the block be directed out of the native Ethernet port on the CPU..
Was this helpful?
What can we do to improve the information ?