Technical FAQs

Ask a Question

Can I tell what the Modbus Plus address of my Modicon PLC is via 984 ladder logic?

Yes, word 2 of the MSTR Instruction Function Code #3 (Get Local Statistics) will give you the Modbus Plus Network address of the PLC.
Below is a example of a MSTR Instruction using Function Code #3 (Get Local Statistics) to get the Modbus Plus address of the PLC

400001 = 3 (Operation Type)
400003 = 1 (length)
400004 = 2 (Offset)
400010 = 2 (Network address of this station)


Legacy KB System (APS) Data: RESL1570 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modbus Plus
Was this helpful?
What can we do to improve the information ?