Technical FAQs

Ask a Question

What does a yellow warning triangle with no text message mean in Concept?

When a yellow warning triangle is displayed in Concept it usually occurs when opening a section of IEC LD.
The source of the warning fault is a vertical or horizontal short has been placed on top of an existing
short. The logic is not affected and will execute as designed. The problem can be corrected by performing
a 'select all' on the section, cutting and then pasting the logic back into the section.

Was this helpful?
What can we do to improve the information ?