Why are my counts more than double as expected on my AS-B882-239?

The AS-B882-239 defaults to BIN for the data type, it needs to be set up as BCD.


Legacy KB System (APS) Data: RESL1166 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon 1/2/3/4/5/8/984s