How is differential protection calculated for a VAMP 265 relay?

Differential protection stage in VAMP 265 is based on fundamental frequency phasors which are calculated using discrete Fourier transforms (DFT). The sampling rate is 32 samples per cycle and the DFT sampling window width is one cycle. The fundamental frequency current phasors are calculated every ten milliseconds.