Wrench 1 on the front display and the CCA634 module on a SEPAM is not recognized.

This is due to the hardware on the SEPAM. In order to use a CCA634 the serial numbers below must be meet:
SEPAM 20 with serial number greater than 0301001
SEPAM 40 with serial number greater than 0623001
SEPAM 80 with serial number greater than 0629001
As a side note the CCA634 is not compatible with the following:
CSH30
CSH120
CSH200
ACE990
GO110