How to time synchronize PM800 or Sepam series device with PowerLogic SCADA?

You can manually do it following the procedure as per below.

a. You must login with operator2, engineer, administrator or kernel user level.

b. Click on a device à List à Resets as per below.

c. Click on Activate from Device Date/Time as per below.

d. Click on OK


Please check also Updated information with our Powerlogic L3 Team


Original Author: YJ


All content © 1992-2009 Schneider Electric

Legacy KB System (APS) Data: RESL200959 V1.0, Originally authored by KBAdPM on 01/08/2010, Last Edited by KBAdPM on 01/08/2010
Related ranges: Sepam series 80, Sepam series 40, Sepam series 20, PM800 series, PowerLogic SCADA 7.1