Why is the label for the SEPAM Series 80 printing vertically and not horizontally?

The Sepam Series 80 with an Integrated UMI has a label running horizontally from left side to right side, but the Sepam Series 80 with Mimic-based UMI has a label running vertically from top to bottom. Therefore, the direction of the label depends on whether Advanced UMI or Mimic-based UMI is selected in SFT2841. If SFT2841 is printing the label vertically, then SFT2841 is configured to use a "Mimic-based UMI" model. In order to modify this setting so that the label prints horizontally, access SFT2841 "offline" or "online". Under the "Sepam hardware" tab, select "Integrated UMI" for the device model.

Once applied, click on Sepam -> Print label. This will print the label vertically.



AEDL3


 

Legacy KB System (APS) Data: RESL200917 V1.0, Originally authored by MiZe on 01/06/2010, Last Edited by MiZe on 01/06/2010
Related ranges: Sepam series 80