Technical FAQs

Ask a Question

The green light on the ACE9XX communication module is permanently ON but the Sepam Series 20, 40 and 80 relay cannot communicate over the network.

If the green led stays lit on the ACE9xx module that means there is a comms wiring issue. For normal working conditions, the green light would be:
a) turned off when Stand-By i.e. Commubnication frame to SCADA
b) flickering when communicating to SCADA


In order to fix the wiring issue, verify:

a) That the module is not grounded more than once. Often, the shield is exposed and grounded unnecessarily with the clamp, which is located below the terminals. Make sure that the shield isn't exposed and touching this clamp.


b) That the RS485 terminals are wired correctly. Here are the wiring diagrams for 2-wire and 4-wire communication:
For 2 wires:
Warning: L+ connects to L- and vise-versa when communicating to a powerlogic or third-party device on the same daisy chain!!!!


  • For 4 wire:

     
  • AEDL3

Date Created: March 4, 2008
Last Revised: September 11, 2008
Public
Original Author: JJ
All content © 1992-2008 Schneider Electric

Legacy KB System (APS) Data: RESL192741 V1.0, Originally authored by PhHa on 09/12/2008, Last Edited by PhHa on 09/12/2008
Related ranges: ACE 9XX
Was this helpful?
What can we do to improve the information ?