Technical FAQs

Ask a Question

What is the minimum cancelling time of the power supply voltage for the Sepam 1000+ without its reinit (restart)?

Effects of interruptions of the DC power supply. (CEI60255-11)
The effects are determined for an interruption with a duration chosen in the following list and declared by the manufacturer : 2 _ 5 _10 _ 20 _ 50 _ 100 _ 200 ms

The interruption must be sudden, i.e.the auxiliary power supply must vary from 0 to the rated value and the opposite .

The relay must not change erroneously its output status when the power supply value is applied or cancelled.

Fugitive cancellings Sepam 1000+ S20: 10ms.
Fugitive cancellings Sepam 1000+ S40: 20ms.
Fugitive cancellings Sepam Series 80: 100ms

Re-published to revised security level: 17 June 2008 by DRM

Applies To: Sepam 20, 40, and 80

Public

All content © 1992-2008 Schneider Electric


Legacy KB System (APS) Data: RESL166865 V2.0, Originally authored by FrKr on 06/18/2008, Last Edited by DaMi on 06/18/2008
Related ranges: Sepam series 40, Sepam series 20
Was this helpful?
What can we do to improve the information ?