What is the difference between QMB and QMJ fusible branch units?

QMJ switches are suitable for use with Class J fuses only. 600 Vac QMB switches can be modified to accommodate Class J fuses by moving the fuse base. Additionally, 100 through 400 ampere QMJ switches will be physically smaller than an equivalent QMB switch.